Calculate Ability
Trade Calculators

Wire Gauge / Electrical Load Calculator

Recommended AWG, load in watts and voltage drop.

Inputs

Given
V
A
ft
%

Results

Computed

Recommended copper conductor

8 AWG

Ampacity 50 A at 75°C · 16,510 circular mils

Minimum size by ampacity10 AWG
Voltage drop on this run4.69 V
Voltage drop percentage1.95%
Load7,200 W
Apparent power7.20 kVA
Voltage at the load235.3 V

Sizes assume copper conductors at 75°C in a normal ambient with no more than three current-carrying conductors in a raceway. Derate for heat, bundling, or aluminium.

8 AWG · 1.95% drop · 7.20 kW

FIG. 5 — VOLTAGE DROP OVER A RUN
PANELLOADI (AMPS)DROP = 2 × L × I × R — ROUND TRIP LENGTHKEEP ≤ 3% ON BRANCH CIRCUITS

How this is calculated

Conductor selection has to satisfy two separate limits. The first is ampacity: the conductor must safely carry the current without overheating, which comes from published tables for copper at a given insulation temperature rating. The second is voltage drop over the length of the run.

Vdrop = (2 × K × I × L) ÷ circular mils  (single phase)

Vdrop = (√3 × K × I × L) ÷ circular mils  (three phase)

K is the resistivity constant, about 12.9 ohm-circular-mils per foot for copper at 75°C. L is the one-way run length; the factor of 2 on a single-phase circuit accounts for current travelling out and back.

Load is calculated from voltage, current and power factor:

watts = V × I × PF  (single phase)  |  watts = √3 × V × I × PF  (three phase)

The recommendation shown is the smallest conductor that meets both the ampacity requirement and your voltage drop target. Always confirm against the current edition of your local electrical code, and derate for high ambient temperature, conduit fill, or aluminium conductors, which need roughly one to two sizes larger than copper for the same load.

Worked example

Feeding a detached garage subpanel

  1. A 60 A, 240 V single-phase subpanel sits 100 ft from the main panel.
  2. Load = 240 V × 60 A = 14.4 kW available at the panel.
  3. Copper 4 AWG carries 60 A comfortably at typical insulation ratings.
  4. Over 200 ft of round-trip conductor, 4 AWG drops roughly 4.9 V at full load — about 2.1% of 240 V.
  5. That sits under the common 3% branch-circuit guideline, so 4 AWG works; at 150 ft you would step up to 2 AWG.

Common mistakes

  • Using one-way length

    Voltage drop happens over the full circuit — out and back. Entering the one-way distance instead of the round-trip length understates the drop by half.

  • Confusing ampacity with voltage drop

    A wire can be thick enough to carry the current safely yet still drop too much voltage on a long run. Ampacity protects against heat; drop protects equipment. Long runs are usually drop-limited.

  • Ignoring aluminum vs copper

    Aluminum has about 61% of copper's conductivity, so the same load needs roughly two AWG sizes larger. Feeder runs often use aluminum for cost — check the gauge against the right material.

What to do with this result

Frequently asked questions